Design and Performance Analysis of an Automatic Solar PV–Grid Power Transfer System Based on Battery Voltage for the Hidroguard System

Authors

  • Ferry Aldi Ardiansyah Universitas Muria Kudus
  • Noor Yulita Dwi Setyaningsih Program Studi teknik Elektro, Universitas Muria Kudus

Abstract

The Hidroguard system requires a stable supply of electrical energy to operate the circulation pump, sensors, microcontrollers, and monitoring devices continuously. The use of the Solar Power Plant (PLTS) system as the main source has limitations because energy production is affected by weather conditions and the energy stored in the battery. This study analyzes Low Voltage Disconnect (LVD) as a controller of automatic energy transfer from the PLTS-battery line to the PLN network through a 12 VDC adapter. The system uses  a 240 Wp monocrystalline solar panel  and a 12 V 150 Ah LiFePO4battery. The experimental method was carried out by observing the battery voltage, LVD contact conditions, relay work, and active energy sources.  The LVD set point is set at 11 V. The PV line remains active at a battery voltage of 13.2 V to 11 V. When the voltage is recorded to drop to 10.8 V, the LVD disconnects the battery line and shifts the Hydroguard load to the PLN network through an adapter. The load returned to the solar power line after the battery voltage increased to 11.5 V. During the 48-hour observation, the application of LVD was able to maintain the continuity of energy supply while protecting the battery from over-discharging conditions. Based on the six conditions of energy source transfer testing, the entire transfer process takes place according to the control logic so that a system success rate of 100% is obtained.